Duenne is not an offiicial seller for

1SAM350000R1014 – ABB

MS132-25
General Information
Extended Product Type:MS132-25
Product ID:1SAM350000R1014
EAN:4013614400148
Catalog Description:MS132-25 Manual Motor Starter
Long Description:The MS132-25 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 25.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 50 kA at 400 VAC and trip class 10. Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and single-phase applications. The handle is lockable to protect against unauthorized changes. Auxiliary contacts, signaling contacts, undervoltage releases, shunt trips, 3-phase bus bars, power in-feed blocks and terminal spacers are available as accessory.
Ordering
Minimum Order Quantity:1 piece
Customs Tariff Number:85362010
Popular Downloads
Data Sheet, Technical Information:2CDC131021D0202
Instructions and Manuals:2CDC131022M6802
Instructions and Manuals (Part 2):2CDC131060M0202
Ex Operating Instructions:2CDC131063M6801
Time-Current Characteristic Curve:1SAM300505F0014
I²t Characteristic:1SAM300507F0001
1SAM300507F0003
Cut-off Current Characteristic:1SAM300508F0001
1SAM300508F0003
CAD Dimensional Drawing:2CDC001079B0201
Dimension Diagram:1SAM300402F0002
Dimensions
Product Net Width:45 mm
Product Net Height:97.8 mm
Product Net Depth / Length:86.55 mm
Product Net Weight:0.31 kg
Technical
Rated Service Short-Circuit Breaking Capacity (Ics):(230 V AC) 50 kA
(250 V DC) 3 Poles in Series 10 kA
(400 V AC) 50 kA
(440 V AC) 30 kA
(500 V AC) 10 kA
(690 V AC) 3 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):(230 V AC) 50 kA
(400 V AC) 50 kA
(440 V AC) 30 kA
(500 V AC) 10 kA
(690 V AC) 3 kA
Rated Instantaneous Short-Circuit Current Setting (Ii):375 A
Setting Range:20 … 25 A
Rated Operational Power AC-3 (Pe):(400 V) Three Phase 11 kW
Rated Operational Power AC-3e (Pe):(400 V) Three Phase 11 kW
Rated Operational Voltage:Main Circuit 690 V AC
Main Circuit 250 V DC
Rated Operational Current (Ie):25 A
Rated Operational Current AC-3 (Ie):25 A
Rated Operational Current AC-3e (Ie):25 A
Rated Operational Current DC-5 (Ie):25 A
Rated Frequency (f):Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage (Uimp):Main Circuit 6 kV
Rated Insulation Voltage (Ui):690 V
Power Loss:at Rated Operating Conditions per Pole 1.8 … 2.8 W
Number of Poles:3
Conventional Free-air Thermal Current (Ith):Main Circuit 25 A
Degree of Protection:Housing IP20
Main Circuit Terminals IP10
Pollution Degree:3
Electrical Durability:50000 cycle
Mechanical Durability:100000 cycle
Terminal Type:Screw Terminals
Connecting Capacity Main Circuit:Flexible with Ferrule 1/2x 0.75 … 6 mm²
Flexible with Insulated Ferrule 1/2x 0.75 … 6 mm²
Flexible 1/2x 1 … 2.5 mm²
Flexible 1/2x 2.5 … 6 mm²
Rigid 1/2x 1 … 2.5 mm²
Rigid 1/2x 2.5 … 6 mm²
Tightening Torque:Main Circuit 2 N·m
Wire Stripping Length:Main Circuit 10 mm
Recommended Screw Driver:Pozidriv 2
Mounting Position:1 … 6
Mounting on DIN Rail:TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance:Electrical Conductive Board, Horizontal – Up to 400 V 0 mm
Electrical Conductive Board, Horizontal – Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
Actuator Type:Rotary Handle
Contact Position Indication:ON / OFF / TRIP
Standards:IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
Remarks:UL508 Self-Protected Combination Motor Controller (Type E) in combination with feeder block S1-M3-xx
Technical UL/CSA
Short-Circuit Current Rating (SCCR):Manual Self-Protected Combination Controllers (Type E), (480Y / 277 V AC) 30 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 35 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 35 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 30 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 18 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 30 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 18 kA
Maximum Operating Voltage UL/CSA:Auxiliary Circuit 250 V AC/DC
Main Circuit 600 V AC
Horsepower Rating UL/CSA:(200 V AC) Three Phase 5 Hp
(208 V AC) Three Phase 7.5 Hp
(220 … 240 V AC) Three Phase 7.5 Hp
(440 … 480 V AC) Three Phase 15 Hp
(550 … 600 V AC) Three Phase 20 Hp
Full Load Amps Motor Use:(200 V AC) Three Phase 17.5 A
(208 V AC) Three Phase 24.2 A
(220 … 240 V AC) Three Phase 22 A
(440 … 480 V AC) Three Phase 21 A
(550 … 600 V AC) Three Phase 22 A
Locked Rotor Amps:(200 V AC) Three Phase 105.8 A
(208 V AC) Three Phase 140 A
(220 … 240 V AC) Three Phase 127 A
(440 … 480 V AC) Three Phase 116 A
(550 … 600 V AC) Three Phase 116 A
General Use Rating UL/CSA:(600 V AC) 25 A
Connecting Capacity Main Circuit UL/CSA:Flexible 1/2x 16-8 AWG
Stranded 1/2x 16-8 AWG
Tightening Torque UL/CSA:Main Circuit 18 in·lb
Environmental
Ambient Air Temperature:Around the Enclosure 0 … +40 °C
Operation -25 … +70 °C
Operation Compensated -25 … +60 °C
Storage -50 … +80 °C
Ambient Air Temperature Compensation:Yes
Maximum Operating Altitude Permissible:2000 m
Resistance to Shock acc. to IEC 60068-2-27:11 ms Pulse 25g
Resistance to Vibrations acc. to IEC 60068-2-6:5g / 3 … 150 Hz
RoHS Status:Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Certificates and Declarations (Document Number)
ABS Certificate:1SAA963001-0101
ATEX Certificate:1SAA963000-3902
BV Certificate:1SAA963001-0202
CB Certificate:1SAA963002-2002
CQC Certificate:CQC2010010307387700
CQC2019010307243864
cUL Certificate:cUL_E137861
cUL_E345003
cULus Certificate:cUL_E137861
Cut-off Current Characteristic:1SAM300508F0001
1SAM300508F0003
Declaration of Conformity – CCC:2020980307003526
2020980307003041
Declaration of Conformity – CE:1SAD101100-3402
Declaration of Conformity – UKCA:1SAD201100-3402
DNV GL Certificate:1SAA963001-0304
EAC Certificate:1SAA963000-2701
Environmental Information:1SAC200049H0009
I²t Characteristic:1SAM300507F0001
1SAM300507F0003
IECEx Certificate:1SAA963000-4001
Instructions and Manuals:2CDC131022M6802
Instructions and Manuals (Part 2):2CDC131060M0202
KC Certificate:1SAA963002-1502
LR Certificate:1SAA963001-0502
RINA Certificate:1SAA963002-0802
RMRS Certificate:1SAA918000-0704
RoHS Information:1SAD101100-3402
Time-Current Characteristic Curve:1SAM300505F0014
UL Certificate:UL_E137861
UL_E345003
Container Information
Package Level 1 Units:box 1 piece
Package Level 1 Width:92 mm
Package Level 1 Depth / Length:102 mm
Package Level 1 Height:50 mm
Package Level 1 Gross Weight:0.325 kg
Classifications
Object Classification Code:F
ETIM 4:EC000074 – Motor protective circuit-breaker
ETIM 5:EC000074 – Motor protective circuit-breaker
ETIM 6:EC000074 – Motor protection circuit-breaker
ETIM 7:EC000074 – Motor protection circuit-breaker
ETIM 8:EC000074 – Motor protection circuit-breaker
eClass:V11.0 : 27370401
UNSPSC:39121521
IDEA Granular Category Code (IGCC):4845 >> 3 Pole Motor Circuit Protector Circuit Breakers
E-Number (Finland):3705998
E-Number (Sweden):3112129

From: 40,00  EXCL.

Disponibile

Bestsellers: