EL3202 – BECKHOFF
EL3202 | EtherCAT Terminal, 2-channel analog input, temperature, RTD (Pt100), 16 bit
The EL3202 analog input terminal facilitates the direct connection of two resistance sensors. The measured resistance value can either be output directly in ohms or transformed into a temperature. If the temperature at the measuring point is of interest, the conversion from resistance to temperature can be carried out in the terminal according to various sensor characteristics (Pt100, Pt1000, NI120, NI1000, KTY types, etc.). The EL3202 can operate sensors in 2- and 3-wire technology, for the 2-wire connection an external bridge is necessary. The EtherCAT Terminals indicate their measurement capability by means of light emitting diodes and status bits in the EtherCAT process image.
Number of inputs 2
Power supply via the E-bus
Technology 2-, 3-wire (default setting: 3-wire)
Distributed clocks –
Input filter limit frequency typ. 1 kHz
Sensor types Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1/4 kΩ), KTY sensors (types see documentation)
Connection method 2- or 3-wire (default: 2-wire)
Resolution 0.1 °C per digit
Conversion time approx. 85 ms default setting, 2…800 ms configurable
Temperature range -200…+850 °C (Pt sensors); -60…+250 °C (Ni sensors)
Measuring current < 0.5 mA (load-dependent)
Measuring error < ±0.5 °C for Pt sensors
Electrical isolation 500 V (E-bus/signal voltage)
Current consumption power contacts –
Current consumption E-bus typ. 190 mA
Bit width in the process image 2 x 32 bit RTD input
Special features integrated digital filter, limit value monitoring, variable connection technology
Weight approx. 60 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
Protect. rating/installation pos. IP20/variable
Pluggable wiring for all ESxxxx terminals
Approvals/markings CE, UL, ATEX
Ex marking II 3 G Ex nA IIC T4 Gc
Design form compact terminal housing with signal LEDs
Material polycarbonate
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Installation on 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means of double slot and key connection
Marking labeling of the BZxxx series
Wiring solid conductor (e), flexible conductor (f) and ferrule (a): spring actuation by screwdriver
Connection cross-section s*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm² s*: 0.08…1.5 mm²,
st*: 0.08…1.5 mm²,
f*: 0.14…1.5 mm²
Stripping length 8…9 mm
Current load power contacts Imax: 10 A