EL3318 – BECKHOFF
EL3318 | EtherCAT Terminal, 8-channel analog input, temperature, thermocouple, 16 bit
The EL3318 analog input terminal allows eight thermocouples to be connected directly and is thus particularly suitable for space-saving use in control cabinets. The EtherCAT Terminal circuit can operate thermocouple sensors using the 2-wire technique. A microprocessor handles linearization across the whole temperature range, which is freely selectable. The error LEDs indicate a broken wire. Compensation for the cold junction is made through an internal temperature measurement at the terminal. The EL3318 can also be used for mV measurement.
The HD EtherCAT Terminals (High Density) with increased packing density feature 16 connection points in the housing of a 12 mm terminal block.
Number of inputs 8
Technology Temperature measurement (TC)
Connection method 2-wire
Signal type differential
Temperature measurement (thermocouple) type B, C, E, J, K, L, N, R, S, T, U (default setting: type K)
Measurement uncertainty (temperature measurement) at 23 °C ambient temperature, with internal cold junction, according type: B: ±6.3 °C; C: ±4.9 °C; E: ±3.1 °C; J: ±3.2 °C; K: ±3.4 °C; L: ±3.1 °C; N: ±3.4 °C; R: ±5.2 °C; S: ±5.4 °C; T: ±3.3 °C; U: ±3.2 °C; for further details see documentation
Voltage measurement ±30/±60/±75 mV
Measurement uncertainty (voltage measurement) at ±75 mV, 23 °C ambient temperature: < ±0.096 % (relative to full scale value)
Resolution 16 bit, representation adjustable: 0.1/0.01 °C or 1/2/4 µV per digit
Input filter limit frequency typ. 1 kHz
Conversion time approx. 2.5 s up to 20 ms, depending on configuration and filter setting, default: approx. 250 ms
Power supply via the E-bus
Current consumption E-bus typ. 210 mA
Electrical isolation 500 V (E-bus/signal voltage)
Special features channel by channel wire break detection, internal and external cold junction, firmware filter adjustable
Weight approx. 70 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Approvals/markings CE, UL, ATEX, IECEx, cFMus
Ex marking ATEX:
II 3 G Ex nA IIC T4 Gc
cFMus:
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx ec IIC T4 Gc
Design form HD (High Density) housing with signal LEDs
Material polycarbonate
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Installation on 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means of double slot and key connection
Marking labeling of the BZxxx series
Wiring solid conductors (e): direct plug-in technique; fine-stranded conductors (f) and ferrule (a): spring actuation by screwdriver
Connection cross-section s*: 0.08…1.5 mm²,
st*: 0.25…1.5 mm²,
f*: 0.14…0.75 mm²
Connection cross-section AWG s*: AWG 28…16,
st*: AWG 22…16,
f*: AWG 26…19
Stripping length 8…9 mm
Current load power contacts Imax: 10 A
From: 612,00 € EXCL.