Duenne is not an offiicial seller for

KL4002-0000 – BECKHOFF

Technology single-ended
Number of outputs 2
Power supply via the K-bus
Signal voltage 0…10 V
Load > 5 kΩ (short-circuit proof)
Output error < ±0.1 % (relative to end value) Resolution 12 bit Conversion time ~ 1.5 ms Electrical isolation 500 V (K-bus/signal voltage) Current consumption power contacts – (no power contacts) Current consumption K-bus typ. 75 mA Bit width in the process image output: 2 x 16 bit data (2 x 8 bit control/status optional) Configuration no address or configuration setting Weight approx. 85 g Operating/storage temperature -25…+60 °C/-40…+85 °C Relative humidity 95 %, no condensation Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27 EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4 Protect. rating/installation pos. IP20/variable Pluggable wiring for all KSxxxx Bus Terminals Approvals/markings CE, UL, ATEX Ex marking II 3 G Ex nA IIC T4 Gc

From: 680,00  EXCL.

Disponibile

Bestsellers: