Duenne is not an offiicial seller for

NZM1-XRAV – EATON

SUPPLY PROGRAM
Assortment
Accessories
accessories
Rear drive
Standard / Approval
UL / CSA, IEC
Size
NZM1
Description
For direct, rear mounting of the switch on the wall or on the door of the electrical cabinet.
Rear operation of the switch through the wall or door of the electrical cabinet.
For lever switches
Degree of protection
IP66, UL / CSA Type 4X, Typ12
use with
NZM1, N1, NS1, PN1
Padlockability
padlockable in position 0 on the handle with max. 3 padlocks
Note
External label for danger can be inserted.

Not in connection with semi-removable plug system or remote control.

Not in connection with auxiliary contact / voltage release with terminals on the left side of the circuit-breaker

DESIGN VERIFICATIONS ACCORDING TO IEC / EN 61439
IEC / EN 61439 design verifications
10.2 Suitability of materials and components
10.2.2 Corrosion resistance
The requirements of the product standard are met.
10.2 Suitability of materials and components
10.2.3.1 Resistance of the enclosure to heat
The requirements of the product standard are met.
10.2 Suitability of materials and components
10.2.3.2 Resistance of insulating materials to normal heat levels
The requirements of the product standard are met.
10.2 Suitability of materials and components
10.2.3.3 Resistance of insulating materials to extraordinary heat levels
The requirements of the product standard are met.
10.2 Suitability of materials and components
10.2.4 Resistance to UV radiation
The requirements of the product standard are met.
10.2 Suitability of materials and components
10.2.5 Lifting
Not relevant as the whole electrical panel needs to be evaluated.
10.2 Suitability of materials and components
10.2.6 Impact test
Not relevant as the whole electrical panel needs to be evaluated.
10.2 Suitability of materials and components
10.2.7 Lettering
The requirements of the product standard are met.
10.3 Degree of protection of the enclosures
Not relevant as the whole electrical panel needs to be evaluated.
10.4 Airborne and superficial dispersion routes
The requirements of the product standard are met.
10.5 Protection against electric shock
Not relevant as the whole electrical panel needs to be evaluated.
10.6 Flush mounting of devices
Not relevant as the whole electrical panel needs to be evaluated.
10.7 Internal circuits and connections
It is the responsibility of the manufacturer of the electrical panel.
10.8 Connections for conductors introduced from outside
It is the responsibility of the manufacturer of the electrical panel.
10.9 Insulation characteristics
10.9.2 Dielectric strength at mains frequency
It is the responsibility of the manufacturer of the electrical panel.
10.9 Insulation characteristics
10.9.3 Impulse withstand voltage
It is the responsibility of the manufacturer of the electrical panel.
10.9 Insulation characteristics
10.9.4 Verification of enclosures in insulating material
It is the responsibility of the manufacturer of the electrical panel.
10.10 Heating
The superheat calculation is the responsibility of the electrical panel builder. Eaton provides equipment dissipation data.
10.11 Resistance to short circuit
It is the responsibility of the manufacturer of the electrical panel. Observe the default values ​​of the equipment.
10.12 EMC
It is the responsibility of the manufacturer of the electrical panel. Observe the default values ​​of the equipment.
10.13 Mechanical function
For the device, the requirements are met if the information in the installation instructions (IL) is observed.
TECHNICAL DATA ACCORDING TO ETIM 8.0
low voltage electrical appliances (EG000017) / Handle for protection switch (EC000229)
Technique Of Ar., Electr., Energy, Tecn. Switchgear, Network And Pipeline Processes / Low Voltage Switching Technology / Power Switches (Ns, <1 Hp) / Handle for Control Units (ecl@ss10.0.1-27-37-04-14 [AKF012014 ]) with restart interlock no With key lock no lock with padlock Yes color black suitable for emergency stop no with axis no suitable for circuit breaker Yes suitable for load disconnector Yes type of protection (NEMA) 4X, 12 APPROVALS Product Standards UL489; CSA-C22.2 No. 5-09; IEC60947, CE marking UL File No. E140305 UL Category Control No. DIHS CSA File No. 022086 CSA Class No. 1437-01 North America Certification UL listed, CSA certified Degree of Protection IEC: IP66, UL / CSA Type 4X, 12

From: 95,00  EXCL.

Disponibile

Available on backorder

Bestsellers: