Duenne is not an offiicial seller for

ZP-IHK – EATON

ZP-IHK – Auxiliary contact, for PLS, postal Code, PKNM, ZP-A40…-ASA…IHK…WHK, Z-MS, 1N/O+1N/C, 0.5HP
DELIVERY PROGRAM
Basic function
Accessories for combined residual-current/power circuit-breakers
Accessories for miniature circuit-breaker
Basic function accessories
Auxiliary contacts
Application
Switchgear for industrial and advanced commercial applications
Product range
Accessory
Side mounting
for fitting on left to: LS, FI/LS
TECHNICAL DATA
Technical data
Electrical
Contact function
1 NO + 1 NC
Electrical
Rated operational voltage [Ue]
250 V AC
Electrical
Rated frequency [f]
50/60 Hz
Electrical
Rated current [Ie ]
6 A
Electrical
Conventional free air thermal current [Ith]
6 A
Electrical
Rated operational current
AC–13
250 V [Ie ]
3 A
Electrical
Rated operational current
AC-15 [Ie]
2 (250 V AC) A
Electrical
Minimum operating voltage per contact [Umin]
5 V DC
Electrical
Rated impulse withstand voltage [Uimp]
2.5 kV
Mechanical
Mounting width
8.8 (0.5 SU) mm
Mechanical
Degree of protection
Integrated
IP40
Mechanical
Terminals
Lift terminals
Mechanical
Tightening torque of terminal screws
≦ 1.2 Nm
Standards
EN 45545-2; IEC 61373
DESIGN VERIFICATION AS PER IEC/EN 61439
Operating ambient temperature min.
-5 °C
Operating ambient temperature max.
+40 °C
TECHNICAL DATA ETIM 8.0
Devices for distribution board-/surface mounting (EG000062) / Auxiliary device for distribution board devices (EC001286)
Electric engineering, automation, process control engineering / Electrical installation, device / Breaker switch component / Auxiliary contact unit for distribution board (ecl@ss10.0.1-27-14-35-02 [AKE327013])
Device fitting
Universal
Additional equipment
Auxiliary switch
Installed at the factory
No
Width in number of modular spacings
0.5
Number of contacts as normally open contact
1
Number of contacts as normally closed contact
1
Number of contacts as change-over contact
0
Number of fault-signal switches
0
Rated switch current
3 A
Rated voltage
230 V
Voltage type for actuating
AC
With auto test for earth leakage function
No
Suitable for max. number of poles main contact unit (total)
2
Suitable for max. current main contact unit
6 A

From: 8,00  EXCL.