Duenne is not an offiicial seller for

2813538 – PHOENIX

Galvanic Isolators – MINI MCR-SL-IU-4
2813538
MCR 3-way galvanic isolator, for galvanic isolation of analog signals, screw connection, input: 4 mA … 20 mA, output: 0 V … 10 V

Restriction of Use
EMC note EMC: Class A product, see the manufacturer’s declaration in the download area
Product type Isolation amplifier
Number of channels 1
Features of insulation
Overvoltage category II
Degree of pollution 2
Number of channels 1
Galvanic isolation Basic insulation according to EN 61010
Galvanic isolation between input and output Yes
Limit frequency (3 dB) ca. 100 Hz
Maximum power dissipated in nominal conditions 434.3 mW
Response time (10-90%) » 3.5 ms
Maximum thermal coefficient <0.01% / K Typical thermal coefficient <0.002% / K Transmission error ≤ 0.1% (of full scale) Galvanic isolation Input / output / power supply Rated insulation voltage 30 V AC 50 V DC Test voltage 1.5 kV AC (50 Hz, 60 s) Diet Nominal tension 24 V DC Supply voltage range 19.2 V DC ... 30 V DC (Use the bus connector for bridging the supply voltage (ME 6.2 TBUS-2 1.5 / 5-ST-3.81 GN, Art.No. 2869728) , can be snapped onto the 35 mm mounting rail according to EN 60715) Max. Absorbed current <9 mA Absorbed power <200 mW Signal: Current input Number of entrances 1 Configurable / Programmable no Input signal, current 4 mA ... 20 mA Input signal, maximum current 50 mA Current input input resistance ca. 50 Ω Signal: Voltage Output denomination Voltage output Number of outputs 1 Configurable / Programmable no Output signal, voltage 0 V ... 10 V Output signal, maximum voltage 12.5 V Short-circuit current ca. 2 mA Load / load output voltage output ≥ 10 kΩ Ripple <20 mV SS <20 mV SS (at 10 kΩ) Connection Screw connection Stripping length 12 mm Thread M3 Rigid conductor section 0.2 mm² ... 2.5 mm² Flexible conductor section 0.2 mm² ... 2.5 mm² Conductor cross section AWG 26 ... 12 Quoted design Length 6.2 mm Height 93.1 mm Depth 101.2 mm Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 2 Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 2 Case material PBT Environmental conditions Degree of protection IP20 Ambient temperature (operation) -20 ° C ... 65 ° C Ambient temperature (storage / transport) -40 ° C ... 85 ° C Elevated position ≤ 2000 m Permissible air humidity (operation) 5% ... 95% (non-condensing) THERE IS Certificate CE conformity UKCA Certificate UKCA compliance UL, USA / Canada Marking UL 508 Recognized Class I, Div. 2, Groups A, B, C, D T4 Homologation for the naval sector Certificate DNV GL TAA000020N DNV GL data Temperatures B. Humidity B. Vibration B. EMC TO Enclosure Required protection according to the Rules shall be provided upon installation on board Electromagnetic compatibility Compliance with the EMC directive Noise emission EN 61000-6-4 Noise immunity EN 61000-6-2 Note Interference can cause slight deviations. Electrostatic discharges Standards / Provisions EN 61000-4-2 Electrostatic discharges Remarks Take measures against electrostatic discharge. High frequency electromagnetic fields Name High frequency electromagnetic fields Standards / Provisions EN 61000-4-3 Typical difference from the final value of the measuring range 5% Fast transients (Burst) Name Rapid transient disturbances (Burst) Standards / Provisions EN 61000-4-4 Typical difference from the final value of the measuring range 5% Surge current load Standards / Provisions EN 61000-4-5 Surge current load Remarks Criterion B Influence conducted Name Interferences Standards / Provisions EN 61000-4-6 Typical difference from the final value of the measuring range 5% Galvanic isolation Basic insulation according to EN 61010 Mounting type Rail mounting Assembly instructions The DIN rail bus connector can be used for bridging the supply voltage, which can be snapped onto the 35 mm DIN rail in accordance with EN 60715. Installation position of your choice

From: 144,00  EXCL.

Disponibile

Bestsellers: